Skip to content
LTE Électrique

Renovation and projects· 6 min read· Sources checked on October 20, 2026

Bathrooms: where outlets, switches and heating go under the Code

In a bathroom, everything is measured from the tub, the shower and the sink: an outlet within 1 m of the sink but at least 1 m from the tub or shower, GFCI protection within 1.5 m of water, and switches and thermostats 1 m from the tub or shower unless protected. The 2026 Code relaxes the rules for heating. Here are the distances, in one table.

French version reviewed by William Letendre, master electrician, on October 21, 2026

In short

  • An outlet within 1 m of the sink, and at least 1 m from the tub or shower (500 mm minimum if that’s impossible).
  • Any ordinary outlet within 1.5 m of a sink, tub or shower is protected by a Class A GFCI.
  • Switches and thermostat: at least 1 m from the tub or shower, or closer with protection, but never within their perimeter.
  • 2026 Code: a heater less than 1.8 m above the floor stays 1 m from water, unless it is protected by a Class A GFCI.
  • A whirlpool tub has its GFCI, placed at least 1.5 m from the tub and easy to test.
In this guide
  1. The distances in one table
  2. Outlets
  3. Switches
  4. Heating: more flexible under the 2026 Code
  5. Light fixtures
  6. Whirlpool tubs
  7. Heated floors and fans
  8. The steps of a bathroom renovation
  9. With LTE Électrique

The distances in one table

ItemRuleIf that’s impossible
Sink outletWithin 1 m of the sink—
Outlet and tub or showerAt least 1 mReduced, but never below 500 mm
GFCIOrdinary outlets within 1.5 m of a sink, tub or shower—
Light switchAt least 1 m from the tub or showerInside the room, protected by a Class A GFCI
ThermostatAt least 1 m from the tub or showerInside the room, with a Class A GFCI or a Class 2 circuit
Heater less than 1.8 m above the floorAt least 1 m from a sink, tub or showerProtected by a Class A GFCI

Bathroom: the distances to respect

Orange zone: within 1 m of the tub or shower, measured from inside the shell. No outlet, switch or thermostat, except for the exceptions in the guide.

The sink outlet is within 1 m of the sink, and protected by a Class A GFCI (within 1.5 m of water).

Simplified diagram, not exactly to scale: the full rules and their exceptions are in the text.

Outlets

The sink outlet

In bathrooms and powder rooms, an outlet must be installed within 1 m of the sink. It must also be at least 1 m from the tub or shower; if that’s impossible, the distance can be reduced, but not below 500 mm.

GFCI

Any ordinary outlet (5-15R and 5-20R) within 1.5 m of a sink, tub or shower is protected by a Class A GFCI. An outlet behind an appliance, such as a washer in a bathroom with laundry, doesn’t need it if its location makes it inaccessible for a portable appliance.

Switches

A light switch goes at least 1 m from the tub or shower. If that’s impossible, it stays inside the room and is protected by a Class A GFCI. Never inside the perimeter of the tub or shower.

Since the 2026 Code, every switch location controlling a fixed light fixture also has a neutral conductor: an electronic dimmer, an occupancy sensor or a smart switch can be added later without rewiring.

Heating: more flexible under the 2026 Code

The thermostat

  • It goes at least 1 m from the tub or shower, measured horizontally without going through a wall.
  • Closer is allowed inside the room (never within the perimeter) if it is protected by a Class A GFCI or supplied by a Class 2 extra-low-voltage circuit.
  • The old 500 mm minimum is gone, and the sink no longer applies to the control: according to the RBQ, several electronic or smart thermostats didn’t work well with GFCIs.

How to measure the 1 m

According to the RBQ, you measure from the inside of the shell of the tub or shower: that’s the limit a person reaching out can get to. On a podium tub, the wide ledge therefore counts toward the 1 m. The same measurement applies to heaters and switches.

The heater

A heater installed less than 1.8 m above the floor must not be within 1 m of a sink, tub or shower, unless it is protected by a Class A GFCI.

Light fixtures

  • In a damp or wet location, the fixture must be approved for that location and marked accordingly.
  • A recessed fixture in contact with insulation or combustible materials must be approved for that use, IC-rated.

Whirlpool tubs

For a whirlpool tub, therapeutic tubs included:

  • its electrical equipment is protected by a Class A GFCI;
  • that GFCI is placed where it can easily be tested, at least 1.5 m from the tub, unless it is part of an approved factory-built tub and sits behind a screen;
  • its controls are in the room, with an on-off switch behind a screen or at least 1 m from the tub wall, unless they are part of the approved tub.

For a hot tub or a pool, the distances are greater: see our hot tub and pool guide.

Heated floors and fans

Each has its place in the circuit plan: plan them before the tile and drywall, with the rest of the bathroom, and check for space in the panel.

The steps of a bathroom renovation

  1. The plan: we place outlets, switches, thermostat and fixtures according to where the sink, tub and shower go.
  2. The wiring: walls open, before the tile and drywall.
  3. The finishing: devices, cover plates and GFCI tests, once the tile is in.

According to the RBQ, this work must be done by a licensed contractor, even in your own home.

With LTE Électrique

  • We place outlets, switches and the thermostat with you, according to your bathroom layout, before the walls are closed.
  • Free estimate within 24 hours; price announced in advance, fixed or hourly depending on the project; anything unexpected is done only with your approval.
  • Drop cloths, shoe covers and a clean site.
  • 2-year labour warranty.

Frequently asked questions

How far from the tub must the outlet be?
At least 1 m from the tub or shower. If that’s impossible, the distance can be reduced, but not below 500 mm. The outlet must also be within 1 m of the sink.
Does a powder room need an outlet?
Yes: in bathrooms and powder rooms, an outlet must be installed within 1 m of the sink.
Can the thermostat be near the tub?
Since the 2026 Code, yes, within 1 m if it is protected by a Class A GFCI or supplied by a Class 2 extra-low-voltage circuit, but never inside the perimeter of the tub or shower.
Where is the 1 m measured from?
Horizontally, without going through a wall, and according to the RBQ, from the inside of the tub or shower shell: that’s the limit a person reaching out can get to. The same measurement applies to heating and switches.
Can my smart thermostat go near the sink?
The 2026 Code no longer targets the sink for heating controls. The RBQ explains that several electronic or smart thermostats didn’t work well with GFCIs, which made them hard to install near sinks.
Why does the bathroom outlet cut out?
That’s the GFCI: it cuts power when current leaks to ground, often because of moisture or a faulty appliance. Don’t bypass it, and test it once a month with the “test” button.
Can a light fixture go above the shower?
Yes, if it is approved for that damp or wet location and marked accordingly.
Does my whirlpool tub need a GFCI?
Yes: the electrical equipment of a whirlpool tub is protected by a Class A GFCI, placed at least 1.5 m from the tub, where it can easily be tested. Its controls stay in the room.
Can I replace my bathroom outlets myself?
According to the RBQ, electrical work must be done by a contractor holding the appropriate licence, even in your own home.

Sources

About this guide

Written by LTE Électrique, a master electrician’s business in Sherbrooke (RBQ licence 5874-5597-01, CMEQ member). Every rule comes from Québec’s Construction Code or an official source, listed above with the date it was checked. French version reviewed by William Letendre, master electrician, on October 21, 2026.

About us

Cite this guide

To cite this guide, use its title, author and address:

“Bathrooms: where outlets, switches and heating go under the Code”, LTE Électrique, https://www.lteelectrique.com/en/guides/bathroom-electrical-rules, French version reviewed by William Letendre, master electrician, on October 21, 2026.

An electrical project?
We call you back the same day.

Call or text 819 570-9836. Free estimate within 24 hours, anywhere in Sherbrooke and the Eastern Townships.

Monday to Friday, 8 a.m. to 4 p.m.

5.0 from 43 Google reviews