Finishing a basement: outlets, circuits, alarms and the sump pump

Finishing a basement is almost like wiring a whole floor: an outlet within 1.8 m of every point along the walls, arc-fault protected circuits, the laundry room, room-by-room heating, interconnected smoke alarms and a well-placed sump pump outlet. The 2026 Code adds rules for flood zones. Plan it all before closing the walls.

French version reviewed by William Letendre, master electrician, on October 21, 2026

In short

  • Along the floor, no point on a usable wall more than 1.8 m from an outlet, and an outlet in any wall space of 900 mm or more.
  • Arc-fault (no more than 10 outlets per circuit) and tamper-resistant outlets; the sump pump can have a dedicated, marked single outlet without arc-fault protection.
  • Laundry: a duplex outlet for the washer and another in the room; the utility room gets its duplex outlet, on its own circuit.
  • Each enclosed heated room has its own thermostat, and under an insulated ceiling, pot lights in contact with insulation are IC-rated.
  • In a designated flood zone: ground-fault protection below grade, and a pump outlet above the flood level or approved for immersion.
In this guide
  1. Basement rules at a glance
  2. Outlets in finished rooms
  3. Laundry and utility room
  4. The sump pump
  5. Flood zones: what the 2026 Code adds
  6. Heating
  7. Lighting and wiring
  8. Smoke alarms
  9. A basement apartment
  10. Panel capacity
  11. Before closing the walls
  12. With LTE Électrique

Basement rules at a glance

ItemWhat the rules call for
Walls of finished roomsNo point along the floor more than 1.8 m from an outlet; an outlet in any wall space of 900 mm or more
Outlet circuitsArc-fault, no more than 10 outlets per circuit; tamper-resistant outlets
LaundryA duplex outlet for the washer, another in the room, a dedicated circuit; GFCI within 1.5 m of the laundry tub
Utility roomAt least one duplex outlet, on its own circuit
Sump pumpDedicated, marked single outlet: allowed without arc-fault
HeatingOne thermostat per enclosed heated room
Pot lights under insulationIC-rated

Outlets in finished rooms

1.8 m and 900 mm

Along the floor, no point on a usable wall may be more than 1.8 m from an outlet. And any usable wall space at least 900 mm wide, between two doors for example, gets its own outlet. A furniture plan helps put them where you’ll need them.

Arc-fault and tamper-resistant

125 V outlet circuits of 20 A or less in a dwelling are arc-fault protected, with no more than 10 outlets per circuit (a Québec rule), and outlets are tamper-resistant. When outlets are added to an existing circuit without this protection, an arc-fault outlet installed as the first added outlet is enough: the whole circuit doesn’t need protection.

Outlets along the walls of a finished room

Along the floor, no point on a usable wall more than 1.8 m from an outlet: no more than 3.6 m between two outlets.

A usable wall space of 900 mm or more, between a door and a corner for example, gets its own outlet.

Simplified diagram, not exactly to scale: the full rules and their exceptions are in the text.

Laundry and utility room

  • At least one duplex outlet where the plumbing is planned for the washer, and at least one more duplex outlet in the laundry room.
  • At least one dedicated circuit for the laundry room outlets.
  • Outlets within 1.5 m of a laundry tub are protected by a Class A GFCI, except the one behind the washer or dryer if it is inaccessible.
  • The dryer has its own circuit, sized for it: it is a continuous load.
  • The utility room gets at least one duplex outlet, on a circuit dedicated to it.

The sump pump

A single outlet reserved for the pump, on its own circuit and permanently marked as a sump pump outlet, may do without arc-fault protection.

Flood zones: what the 2026 Code adds

The 2026 Code covers installations in flood-risk zones for the first time:

  • circuits below grade get ground-fault protection;
  • the sump pump outlet is above the flood level, or marked as suitable for immersion;
  • service equipment must not be placed below the flood level.

A zone is at risk of flooding under the Code only if the competent authority has designated it: the municipality’s zoning or planning bylaw, or a provincial map. The RBQ recommends checking with the municipality or the RCM.

Heating

  • Each enclosed room containing a heater has its own thermostat, rated at least for the heaters it controls.
  • Baseboards are installed so that framing doesn’t block the heat.
  • Heating circuits are used only for heating. A heating load is continuous: it is limited to 80% of the breaker, unless the breaker is marked for 100%.

Lighting and wiring

  • Under an insulated ceiling, a pot light in contact with insulation must be IC-rated. A non-IC fixture needs 13 mm of clearance from combustible material, and insulation must stay at least 76 mm away.
  • Since the 2026 Code, every switch location controlling a fixed light fixture has a neutral conductor, ready for an electronic dimmer or a smart switch.
  • In an unfinished area, non-metallic sheathed cable isn’t run along the underside of joists without protection, such as a board.

Smoke alarms

In new work, smoke alarms are hard-wired and interconnected on every floor and near bedrooms: when one sounds, they all sound. With a fuel-burning appliance or an attached garage, a carbon monoxide alarm is also required near bedrooms. They go in during rough wiring; our smoke alarm guide says more.

A basement apartment

Under the Code, a dwelling is one or more rooms where people can prepare and eat meals, live and sleep. If the basement becomes one, the dwelling rules apply, and the circuits from its panel feed nothing in the other dwelling. We discuss it at the estimate: it changes the plan.

Panel capacity

In the load calculation, the basement counts at 75% of its area. A bedroom, a kitchenette or extra baseboards can change the result, and panel space matters too: a sub-panel often solves the lack of room, without adding capacity to the service.

Before closing the walls

  1. The plan: rooms, furniture, laundry, heating and alarms.
  2. The load calculation and the panel: capacity and space.
  3. Rough wiring: walls open, before insulation and drywall.
  4. Finishing: devices, cover plates, thermostats and tests.

According to the RBQ, this work must be done by a contractor holding the appropriate licence, even in your own home.

With LTE Électrique

  • We plan the basement with you before the walls are closed; the estimate is free, within 24 hours.
  • Price announced in advance, fixed or hourly depending on the project; anything unexpected is done only with your approval.
  • Drop cloths, shoe covers and a clean site.
  • 2-year labour warranty.

Frequently asked questions

How many outlets does a basement room need?
Enough so that no point along the floor of a usable wall is more than 1.8 m from an outlet. Any usable wall space at least 900 mm wide also gets an outlet.
Does a basement bedroom change anything?
Yes: hard-wired, interconnected smoke alarms near bedrooms in new work, and a carbon monoxide alarm near bedrooms if there is a fuel-burning appliance or an attached garage.
Does my sump pump have to be on an arc-fault circuit?
The 2026 Code allows an exception for a single outlet reserved for the pump, on its own circuit, permanently marked as a sump pump outlet.
Is my house in a flood zone under the Code?
Only if the competent authority has officially designated it: the municipality’s zoning or planning bylaw, or a provincial flood zone map. The RBQ recommends checking with the municipality or the RCM; Québec’s interactive map gives an overview, with no legal value.
I’m adding outlets to an old circuit: does the whole circuit need arc-fault protection?
Not necessarily. Under the Code, if an arc-fault outlet is the first outlet added to the existing circuit, the whole circuit doesn’t have to be protected.
Does the laundry room need its own circuit?
Yes: at least one circuit dedicated to the laundry room outlets. The dryer has its own circuit, sized for it, and it counts as a continuous load.
Does the basement count in the load calculation?
Yes, at 75% of its area in the living area. Adding rooms, a kitchenette or heating can change the result: we redo it before the work.
My basement flooded: can I turn the power back on?
Not before an inspection. The RBQ points out that moisture can damage insulation and that the water may contain contaminants that harm the installation: re-energizing without an assessment carries serious risks.
Can I wire my basement myself?
No: according to the RBQ, electrical work must be done by a contractor holding the appropriate licence, even in your own home.

Sources

About this guide

Written by LTE Électrique, a master electrician’s business in Sherbrooke (RBQ licence 5874-5597-01, CMEQ member). Every rule comes from Québec’s Construction Code or an official source, listed above with the date it was checked. French version reviewed by William Letendre, master electrician, on October 21, 2026.

About us

Cite this guide

To cite this guide, use its title, author and address:

“Finishing a basement: outlets, circuits, alarms and the sump pump”, LTE Électrique, https://www.lteelectrique.com/en/guides/finishing-a-basement-electrical, French version reviewed by William Letendre, master electrician, on October 21, 2026.